Interpretation #7286

Published January 06, 2014

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
4
Section
Table 403.3 Note h
Topic
Nail Salon Ventilation Requirement

Question

Is it the intent of note h in table 403.3 that

all nail stations in beauty salons be equipped

with a source capture ventilation system?

Answer Published 01/06/2014 at 11:36 AM

Yes, footnote (h) reads "For nail salons, the required
exhaust shall include ventilation tables or other systems
that capture the contaminants and odors at their source and
are capable of exhausting a minimum of 50 cfm per station."

Commentary

This footnote specifically references ventilation tables. These tables are equipped with an exhaust connection and some type of capture/containment area to minimize the amount of odors that may escape into the general salon air. Further, a duct needs to be extended to the floor, near the feet, to pick up fumes from pedicures. Other methods acceptible to the building offical may be approved as well.