Interpretation #7284

Published January 06, 2014

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
9
Section
903.2.1.2 Group A-2
Topic
Level of Discharge

Question

Is the level of exit discharge the second story

of a two story building serving an occupancy that

is a fire area separated with a 2-hour horizontal

assembly and 1-hour egress corridor with the two

exits not shared exits with the first floor.

Answer Published 01/06/2014 at 11:33 AM

No

Commentary

Means of egress is comprised of exit access, exit, and exit discharge. In the example in the question, exit access is on the second floor. The exit traverses the second and the first. The discharge is finally on the first floor. The fact that the exit is protected and is not shared with the first floor has no bearing on the question. SECTION 1002 DEFINITIONS EXIT DISCHARGE, LEVEL OF. The lowest level having at least 50 percent of the number of exits and capacity of exits discharging to the exterior at grade or story with the least change in elevation to grade, provided no other story has 50 percent of its exits or egress capacity discharging to the exterior at the grade.