Interpretation #7282

Published January 10, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
7
Section
703.8
Topic
Flashing at exterior window & door openings

Question

Is it the intent of 703.8 1. 1.3 to eliminate the



requirement stated in 1. that the "flashing at



exterior window and door openings shall extend to



the surface of the exterior wall finish...

Answer Published 01/10/2014 at 9:41 AM

Yes unless the standards or instructions provided as part
of the product approval contain the same requirements.

Commentary

If the flashing method is specified in the manufacturers installation instructions that are part of the product approval that is what you would follow. Otherwise the code states that flashing at exterior window and door openings shall be installed in accordance with one or more of the following or other approved method: and then references - In accordance with FMA/AAMA 100, FMA/AAMA 200, or FMA/WDMA 250, so you could follow one of these standards.