Interpretation #7278

Published November 11, 2013

Original Request

Code Version
2010
Code
EXTBLDG
Code Description
Existing Building
Chapter
6
Section
609.1
Topic
Roof top equipment changeout compliance with windload provisions

Question

Is it the intent of section 609 to only comply

with section 301.11 of the 2010 FBC mechanical

for the replacement of roof top mounted HVAC

equipment and not comply with the windload

provisions of mechcanial or building code?

Answer Published 11/11/2013 at 12:03 AM

No, This section of the existing building code refers back

to the section in the mechanical code that covers "repairs"



only. The section you refer to is intended to ensure the

listing of the appliance is not violated and the



efficiency of the system is not diminished. A new piece of

equipment would rightfully need to comply with section

602.4 which would lead to section 301.12 of the FBC
Mechanical

code. This will provide the link to 1609 of the FBC
Building code for the attachments.

Commentary

The existing building volume also contains section 101.5.5 which specifically references existing equipment and prohibits windload and roof clearance compliance requirements enforcement until the equipment is removed or replaced.