Interpretation #7272

Published November 18, 2013

Original Request

Code Version
2010
Code
EXTBLDG
Code Description
Existing Building
Chapter
9
Section
909
Topic
Heating System Required

Question

Is it the intent of Section 909, in the case

when there is a change of occupancy in an

existing building from storage to assembly, to

require installation of space heating system?

Answer Published 11/18/2013 at 2:21 AM

The answer to the question is yes.

Although it appears the code section referenced is

incorrect based on the question and a code was not

specified. See the Commentary below.

Commentary

Section 912 addresses changes of occupancy classification which is clearly the case at hand. Section 912.1.1 requires compliance with Chapter 8 it is being presumed that this is a change of occupancy classification without separation. As a change of occupancy classification without separation, the entire building is required to comply with the new occupancy requirements unless modified by the FBCEB. Chapter 8 states the provisions of Chapters 6 and 7 are applicable in addition to the provisions of Chapter 8. (s.801.2). Section 701.3 requires all new construction elements, components,systems and spaces to comply with the FBCB. In addition, the occupancy classification change constitutes a reconfiguration or conversion as addressed at Section 709.1 FBCEB requiring the installation of appropriate natural or mechanical ventilation and exhaust system in accordance with FBCM.