Interpretation #7269

Published November 08, 2013

Download Final PDF

Original Request

Code Version
2010
Code
EXTBLDG
Code Description
Existing Building
Chapter
5
Section
506
Topic
Structural repairs & dangerous conditions found

Question

Is it the intent of 506.1 that while performing

structural repairs in a work area that unrelated

dangerous conditions in the work area be

eliminated.

Answer Published 11/08/2013 at 1:26 AM

Yes, dangerous conditions discovered during work must be

corrected.

Commentary

If the room has existed for 20 years, proving a dangerous condition exists could be problematic. The building official should be notified and if the building official believes there is a dangerous condition they should conduct an evaluation in accordance with Section 506.2.2.1.