Interpretation #7265

Published October 20, 2013

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Chapter
30
Section
3007.4
Topic

Question

Is it the intent of this section to require the
fire service elevator lobby to be separated from
the occupant evacuation elevator lobby per
3008.11 in a high rise building.

Answer Published 10/20/2013 at 1:26 PM

NO

Commentary

FBC - Building, 1018.6, Exception, specifically allows exit access through lobbies. It is, however, the intent of 3007.4.1 to provide direct access from a fire service elevator lobby (required in a high-rise) to an exit.