Is it the intent of section 401.4.1 to permit the
mechanical air intake for a dwelling unit to be
within 10 feet of a residential bathroom, kitchen
or dryer exhaust? Specifically, can the intake be
located no less than 36 inches away from these
exhaust outlets?
Interpretation #7252
Published November 13, 2013
Original Request
- Code Version
- 2010
- Code
- MECHANIC
- Code Description
- Mechanical
- Chapter
- 4
- Section
- 401.4.1
- Topic
- Separation of air intake and exhaust
Question
Answer Published 11/13/2013 at 7:47 PM
NO. This code section does not contemplate "environmental
air". FMC 401.4 provides a similar option of an intake
opening not less than 3 feet below contaminant sources,
however the application must also comply with 4 other
requirements.
air". FMC 401.4 provides a similar option of an intake
opening not less than 3 feet below contaminant sources,
however the application must also comply with 4 other
requirements.
Commentary
401.4 item #2 references compliance with 501.2.1. 501.2.1
item #3 deals specifically with the termination of
environmental air (which includes domestic dryers, bathroom
exhaust and domestic kitchen exhaust). There is actually a
conflict within the code stipulating the 10 foot separation
in 501.2.1 item #3 and 401.4.1 indicating that bathroom or
kitchen exhaust from a residential dwelling not be
considered a hazardous or noxious contaminant and therefore
potentially exempt from the 10 foot rule of 401.4.1.
The more stringent rule should apply. Thus,the
environmental air exhaust must terminate a minimum of 10
feet from any mechanical ventilation intake location.