Interpretation #7250

Published September 28, 2013

Original Request

Code Version
2010
Code
BUILDING
Code Description
Chapter
12
Section
1204.1 exception
Topic

Question

Is it the intent of 1204.1 to apply to ALL spaces.
Or can the exception be applied to spaces that ARE
NOT INTENDED for human comfort such as an
warehouse area.

Answer Published 09/28/2013 at 4:14 PM

NO

Commentary

The space in question is not intended for human comfort. Therefore, the exception to 1204.1 applies. However, the occupancy must still comply with the Florida Building Code Mechanical Section 401.2.