Is it the intent of Section 1008.1.10 to require
panic hardware or fire exit hardware for a space
with an occupant load of 50 or more in a Group A
or E occupancy?
Interpretation #7248
Published September 28, 2013
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Chapter
- 10
- Section
- 1008.1.10
- Topic
Question
Answer Published 09/28/2013 at 4:12 PM
Yes
Commentary
This is a conflict within the code and the more stringent
would apply per Section 102.1. The base ICC code requires
panic hardware at an occupant load of 50 and does not
contain a Section 1031.
The FFPC requires panic hardware for Group E with an
occupant load of 100. This will not change in the next
edition of the FFPC or the base ICC code.