Interpretation #7248

Published September 28, 2013

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Chapter
10
Section
1008.1.10
Topic

Question

Is it the intent of Section 1008.1.10 to require
panic hardware or fire exit hardware for a space
with an occupant load of 50 or more in a Group A
or E occupancy?

Answer Published 09/28/2013 at 4:12 PM

Yes

Commentary

This is a conflict within the code and the more stringent would apply per Section 102.1. The base ICC code requires panic hardware at an occupant load of 50 and does not contain a Section 1031. The FFPC requires panic hardware for Group E with an occupant load of 100. This will not change in the next edition of the FFPC or the base ICC code.