Interpretation #7240

Published September 28, 2013

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Chapter
Section
909.18.8.3
Topic

Question

Is it the intent of this section to require that
the special inspector for smoke control to be a
different individual then that of the responsible
registered design professional/engineer of
record?

Answer Published 09/28/2013 at 3:53 PM

No















However, If the responsible design professional is to act







as the special inspector, he/she would have to qualify in







accordance with 909.18.2.

Commentary

ASHRAE Guideline 5, COMMISIONING SMOKE MANAGEMENT SYSTEMS ASHRAE Guideline 5 states the following under definitions, COMMISSIONING AUTHORITY: “There are many options as to which party to the commissioning process will be the “authority”. The design professional, contractor, independent commissioning agency, or owner may be the commissioning authority” The designer of the smoke control system is probably the best for inspection of that system. This appears to be a Florida specific amendment incorporating language from the IBC 2012. It was not in the IBC 2009.