Interpretation #7232

Published September 25, 2013

Original Request

Code Version
2010
Code
BUILDING
Code Description
Chapter
4
Section
424.1.5.3
Topic

Question

Is it the intent of 2010 FBC Building section
424.1.5.3 Materials to allow the pool equipment
within the fenced equipment area to be placed on
concrete ?housekeeping? pads, with gravel placed
on the remainder of the enclosed area, instead
of the entire enclosure having a nonabsorbent
floor?

Answer Published 09/25/2013 at 1:28 AM

No

Commentary

424.1.5.3 states that the equipment enclosure, area or room floor shall be of concrete or other nonabsorbent material.... Therefore, the entire fenced equipment area falls under this requirement.