Interpretation #7231

Published September 25, 2013

Original Request

Code Version
2010
Code
BUILDING
Code Description
Chapter
7
Section
707.4
Topic

Question

Is it the intent of Section 707.4 to allow non-
fire rated exterior walls complying with Section
705 to serve as separation between fire areas
(reference also Sections 707.3.9, 901.7, and
903.2.1.2)?

Answer Published 09/25/2013 at 1:25 AM

No. A wall with no fire resistance rating cannot serve to

separate fire areas.

Commentary

In the situation described, as part of the comment, the exerior area would be included within the fire area definition since the definition includes "Areas of the buildng not provied with surrounding walls....if such areas are included within the horizontal projection of the roof...." In order to create separate fire areas, a fire barrier wall would need to be utilized per section 707.3.9 to separate the fire areas to limit square footage.