Interpretation #7229

Published September 25, 2013

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Chapter
3
Section
R310.4
Topic

Question

Is it the intent of R310.4 of the 2010
Residential Building Code to allow the
installation of security bars to windows on a
home that is utilizing the exterior doors as the
Emergency Egress in sleeping rooms.

Answer Published 09/25/2013 at 1:03 AM

Yes, if all sleeping rooms have a code compliant door

leading directly outside. The exterior doors would serve as

the required escape and rescue openings.

Commentary

Bars, grills, covers, screens or similar devices may also be placed over emergency egress windows per the Florida Building Code Residential per section 310.4 if the opening size complies with sections R310.1.1 to R310.1.3 and such devices shall be releasable or removable from the inside without the use of a key, tool, special knowledge or force greater than that which is required for normal operation of the escape and rescue opening.