Interpretation #7223

Published December 10, 2013

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
3
Section
R322.1.6
Topic
flood proofing

Question

Is it the intent of the exception to this code section to allow for a dry flood-proofed below grade space for the limited use of equipment and components?

Answer Published 12/10/2013 at 5:37 AM

No. Electrical systems, equipment and components; heating,

ventilating, air conditioning; plumbing appliances and

plumbing fixtures; duct systems; and other service

equipment are permitted below the flood elevation provided

that they are designed and installed to prevent water from

entering or accumulating within the components and to

resist hydrostatic and hydrodynamic loads and stresses,

including the effects of buoyancy, during the occurrence of

flooding to the design flood elevation in accordance with

ASCE 24. Electrical wiring systems are permitted to be

located below the required elevation provided they conform

to the provisions of the electrical part of this code for

wet locations.

Commentary

Page 22 of ASCE/SEI 24-05, section 6.2.1, "Dry Floodproofing Limitations", "Dry floodproofing of residential structures or residential areas of mixed-use structures shall not be permitted." The commentary on page 52 explains it in more detail.