Interpretation #7215

Published July 30, 2013

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
1
Section
403.3.2
Topic
redundant water supply

Question

Is it the intent of Section 403.3.2 to require redundant water supplies to all high rise buildings or only high rise buildings greater than 420 feet?

Answer Published 07/30/2013 at 10:11 PM

Yes, the provisions of 403.3.2 is applicable to all
High-Rise buildings.

Commentary

The code require two mains for fire pumps for all high rise buildings and there is an Exception. The Exception allows a fire pump to be fed from two connections to the same main (a single main) provided the connection is such that an interruption can be isolated and the water supply will continue uninterrupted.