Interpretation #7212

Published July 22, 2013

Download Final PDF

Original Request

Code Version
2010
Code
ELECTRIC
Code Description
Electrical
Chapter
2
Section
210.12
Topic
Arc Fault Protection

Question

Is it the intent of the requirement for Arc Fault protection in a "dwelling unit" to include those areas when they are part of a fire station?

Answer Published 07/22/2013 at 9:07 PM

Yes. The sleeping / dwelling portions of a fire station are
typically classified as an R-2 occupancy. All 120-volt,
single phase, 15- and 20-ampere branch circuits supplying
any of the rooms or spaces specified in Section 210.12(B) of
the R-2 portion of the fire station are required to be AFCI
protected.

Commentary

None.