Interpretation #7210

Published July 22, 2013

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
30
Section
3006.6
Topic
Condensate Drain in elevator machine room

Question

Is it the intent of of this section to not allow condensate drain piping, including condensate pumps, in an elevator machine room that is removing condensate from an air conditioning unit located in the machine room that serves only the machine room?

Answer Published 07/22/2013 at 9:06 PM

No, a condensate would not be a plumbing system as defined
by the FBC-Plumbing. Therefore, condensate piping and
related pumps for equipment serving only the elevator
equipment room would be allowed.

Commentary

None.