Interpretation #7186
Published June 01, 2013
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 6
- Section
- 602
- Topic
- Exterior Bearing Wall
Question
Is it the intent of Section 602 to allow an exterior bearing wall in a building of Type III-B Construction Type with greater than 30 feet separation from any property line or adjacent structure to be reduced from the 2-hour fire- rating as required in Table 601 to be a 0-hour fire-rating?
Answer Published 06/01/2013 at 10:55 AM
No. The most stringent requirement applies.
Commentary
See informal interpretation #4913.