Interpretation #7177

Published May 31, 2013

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
11
Section
403.2.2.1 Duct tightness.
Topic
Duct Testing

Question

Is it the intent of the Exception in section 403.2.2.1 which states "Duct testing is not mandatory for buildings complying by Section 405 of this code." That compliance using SECTION 405 SIMULATED PERFORMANCE ALTERNATIVE (Performance) that duct testing will never be required since Table 405.5.2 (2)Default Distribution System Efficiencies (DSE) For Proposed Designs. is left as Reserved also TABLE B-1.1.2(1) SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED DESIGNS lists the Proposed Design DSE as .88? Why is there no data for Table 405.5.2 (2)? Is it the intent that the Performance method only be used when the ducts and air handler are both located in conditioned spaces?

Answer Published 05/31/2013 at 12:20 AM

When complying with Section 405, duct testing is not required.
This is a trade-off method and assumes leaking ducts in the
compliance criteria. Unless the form 405-2010 takes a credit
for leak-free duct systems. Then a duct test, or other
methods of compliance would be required.

Commentary

None.