Interpretation #7173

Published May 28, 2013

Original Request

Code Version
2010
Code
PLUMBING
Code Description
Plumbing
Chapter
11
Section
1106
Topic
rain fall rate interpolation

Question

Is it the intent of the code to allow for interpolation of rain fall rates in table 1106.3 as it allows for interpolation in table 1106.2(1)?

Answer Published 05/28/2013 at 6:50 PM

No. If interpolation were to be permitted under Table 1106.3,
without a note expressly allowing it, what would be the
point of the notes associated with 1106.2(1) and 1106.2(2)?
Further, the hydraulics associated with horizontal and
vertical piping are different. Lacking background data
establishing unequivocally that the numbers in Table 1106.3
are linearly related, we must assume that they are not, and
linear interpolation should not be allowed.

Commentary

The "interpolation" referred to in the footnotes of Tables 1106.2(1) and 1106.2 (2)is intended to permit different sizes and shapes other than circular or rectangular pipes to be used for vertical conductors. (See IPC proposal P95-07/08 for further explanation). There is no similar footnote in Table 1106.3 because horizontal storm drainage is typically circular pipe.