Interpretation #7166

Published May 24, 2013

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
4
Section
404.6
Topic
Atriums

Question

Is it the intent of Exception 1 to Section 404.6 Enclosure of Atriums to require automatic sprinklers on both sides of individual windows in a smoke partition separating the atrium from individual spaces?

Answer Published 05/24/2013 at 12:12 PM

yes IF the design of the separation wall has glass that does
not comply with the fire rating requirement of 404.6 and if
there is a walkway on the atrium side and if the openings are
windows, the windows could be protected or designed with rated
glass.

Commentary

None.