Interpretation #7153
Published April 04, 2013
Original Request
- Code Version
- 2010
- Code
- MECHANIC
- Code Description
- Mechanical
- Chapter
- 5
- Section
- 504.8
- Topic
- standby generator
Question
Is it the intent of 504.8 to require a standby generator to power dryer exhaust fans that serve multi-sory common dyer exhaust systems in non- high rise residential buildings?
Answer Published 04/04/2013 at 3:17 PM
Yes. The Florida Mechanical Code 2010 Sec. 504.8- item 7
clearly requires stand by power.
clearly requires stand by power.
Commentary
The purpose is to restict such systems from being able to
act as a chimney stack and allow smoke to get into multiple
other units. Dryer vents are not permitted to have fire or
smoke dampers installed in the ducts. Therefore, if a multi-
story or common venting system is utilized, considerations
have to be made in the gauge of the metal used for venting
and maintaining a negative pressure on the system in the
event a fire happens in the venting system or building.
Chapter 6 has specific exceptions to bathroom and dryer
exhaust in a rated shaft for B and R occupancies.