Interpretation #7144

Published February 22, 2013

Original Request

Code Version
2007
Code
BUILDING
Code Description
Building
Chapter
25
Section
2508.1
Topic
GA-216 gypsum board attachment

Question

Is it the intent of section 2508.1 to use reference you to table 2508.1 in essence guiding you to use GA-216 as the attachment standard for Gypsum Board?

Answer Published 02/22/2013 at 9:27 AM

The section requires compliance with GA-216 for gypsum
board installation. However, if it is a fire resistant
assembly, the terms of the listing must be met or the fire
resistance rating is negated.

Commentary

The maximum spacing of screws from the edge is determined by the required spacing pattern as dictated in the listing.