Interpretation #7140

Published February 22, 2013

Download Final PDF

Original Request

Code Version
2010
Code
FUELGAS
Code Description
Fuel Gas
Chapter
3
Section
310
Topic
CSST bonding

Question

Is it the intent of this section to require CSST tubing to be bonded to the grounding electrode system with a #6 Cu. wire where it enters the building regardless of what type of piping is used to connect the system to the interior system? Would this bond need to be run underground from the grounding electrode to the entrance point of the gas piping?

Answer Published 02/22/2013 at 9:26 AM

Yes. 240.104(B) allows this bonding to take place.
Running the bond wire underground is not a requirement.

Commentary

The use of gas piping as the grounding electrode is not allowed. The manufacturer's installation instructions for the CSST tubing must be followed.