Interpretation #7140
Published February 22, 2013
Original Request
- Code Version
- 2010
- Code
- FUELGAS
- Code Description
- Fuel Gas
- Chapter
- 3
- Section
- 310
- Topic
- CSST bonding
Question
Is it the intent of this section to require CSST tubing to be bonded to the grounding electrode system with a #6 Cu. wire where it enters the building regardless of what type of piping is used to connect the system to the interior system? Would this bond need to be run underground from the grounding electrode to the entrance point of the gas piping?
Answer Published 02/22/2013 at 9:26 AM
Yes. 240.104(B) allows this bonding to take place.
Running the bond wire underground is not a requirement.
Running the bond wire underground is not a requirement.
Commentary
The use of gas piping as the grounding electrode is not
allowed. The manufacturer's installation instructions for
the CSST tubing must be followed.