Interpretation #7130

Published February 25, 2013

Download Final PDF

Original Request

Code Version
2010
Code
EXTBLDG
Code Description
Existing Building
Chapter
9
Section
910.1
Topic
Drinking Fountain for a Change of Occupancy

Question

Is it the intent of section 910.1 to require an

accessible drinking fountain be installed when a

Group R-3 is partially changed to a Group D

occupancy (Family Day Care)?

Answer Published 02/25/2013 at 10:47 PM

Yes, if there is a change of occupancy. 912.8 Accessibility
reads: "Existing buildings that undergo a change of group
or occupancy classification shall comply with the
provisions of the Florida Building Code, Accessibility."

Commentary

If the occupancy changes to "D" - table TABLE 403.1 of the plumbing code requires a drinking fountain and section 202.4.1 of the accessibility code requires it to be accessible.