Interpretation #7129

Published January 31, 2013

Original Request

Code Version
2010
Code
EXTBLDG
Code Description
Existing Building
Chapter
6
Section
611.1
Topic
equipment supports

Question

Is it the intent of paragraph 611.1 that equipment supports be raised or replaced to comply with table 1509.7 of FBC-Building?

Answer Published 01/31/2013 at 2:02 PM

Section 611.1 does not apply as the provisions of FBCB
102.8 apply. In addition, Section 611.1 invokes
compliance with FBCB Chapter 15. FBCB Section 1510 would
apply which invokes Section 1509.7.

Commentary

102.8 Existing mechanical equipment. An agency or local government may not require that existing mechanical equipment on the surface of a roof be installed in compliance with the requirements of the Florida Building Code until the equipment is required to be removed or replaced. 1510.1 General. Materials and methods of application used for recovering or replacing an existing roof covering shall comply with the requirements of Chapter 15. 1509.7 Mechanical units. Roof mounted mechanical units shall be mounted on curbs raised a minimum of 8 inches (203 mm) above the roof surface, or where roofing materials extend beneath the unit, on raised equipment supports providing a minimum clearance height in accordance with Table 1509.7.