Interpretation #7126

Published February 06, 2013

Original Request

Code Version
2010
Code
ELECTRIC
Code Description
Electrical
Chapter
3
Section
340
Topic

Question

Is it the intent of NEC 340, to allow UF cable to be used for dock wiring where it would occasionally be submerged.

Answer Published 02/06/2013 at 11:04 AM

No. NEC 340.12 (10) prohibits the use of UF cable where
subject to physical damage. NEW 340.12 (9) prohibits the
use of UF where exposed in direct sunlight, unless it's
identified as sunlight resistant.

Commentary

Both these prohibitions need to be evaluated by the AHJ in the context of the particular installation that is being inspected, and the listing of the actual material being used.