Interpretation #7125
Published February 05, 2013
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 1
- Section
- 402 Energy Code
- Topic
- Ductwork replacement and 30% rule
Question
For a residential renovation (which exceeds 30% of the structure value) when the existing AHU and ductwork in attic are being replaced as part of the renovation, is it the intent of the Prescriptive Method 402-2010 to prohibit the reinstallation of new ductwork in unconditioned attics? For a residential renovation (which exceeds 30% of the structure value) where there is no existing central ac or ductwork, is the intent of the Prescriptive Method 402-2010 to prohibit the installation of new ductwork in unconditioned attics?
Answer Published 02/05/2013 at 11:31 AM
The answer to the question is probably no. Please see the
comments attached below.
Section 402 discusses only thermal envelope requirements.
Section 403.2 discusses where and how ducts may be
installed in unconditioned attics.
comments attached below.
Section 402 discusses only thermal envelope requirements.
Section 403.2 discusses where and how ducts may be
installed in unconditioned attics.
Commentary
This is not a simple yes/no question as it may seem.
If the project meets the definition of a renovation as
found in FBC-EC Section 202, then certain requirements of
the Energy Conservation Code will apply. Table 101.4.1 for
Nonexempt Existing Buildings, includes a chart for what
building systems and components must comply with the energy
code when installed as new or are replaced.
A 2012 "Glitch fix" to the 2010 Energy Conservation Code
included the following: "403.2 Ducts.403.2.1 Insulation
(Prescriptive) Supply and return ducts, including air
filter enclosures, air ducts and plenums, shall be located
inside the building thermal envelope and All other ducts
shall be insulated to a minimum of R-6."
This provides a disconnect with the Existing Building Code
Level One Alterations Section 601.2 Conformance. Which
allows a building to be altered so long as the replaced
system does not reduce the minimum efficiency of the
structure. This carries forward into Level Two Alterations
(701.2).
In short, the Energy Code would not require the relocation
of ductwork or air handlers to within the thermal envelope
of the structure for a renovation. However, if additional
square footage is being added, then there could be some
application of the more stringent requirements based on
exact system design.
Requiring the relocation of the equipment and duct systems
being replaced as part of a renovation meeting the 30% rule
to comply would appear to be punitive in nature and result
in a gross expense for something that was previously
approved and acceptable.
That being said, the arguement can be made that 402.3 as
written is applicable if the project meets the definition
of a renovation in Section 202. This would mean no AHU or
ducts in unconditioned spaces. However, insulating the roof
deck and sealing off the attic would bring the ducts and
equipment within the thermal envelope of the structure and
therefore meet the requirements of 402.3.
Further reason for the confusion is form 402-2010 on table
402A next to “ductwork & air handling unit” it says “not
allowed”. Section 403.2 discusses where and how ducts may
be installed in unconditioned attics. Section 403.2.4 does
prohibit air handling units from being located in an attic
when using section 402 for compliance.