Interpretation #7104

Published November 19, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
4
Section
437
Topic
Critical Branch Distribution System

Question

Is it the intent of 437.2.8.3 to require a Critical Branch distribution system?

Answer Published 11/19/2012 at 9:43 AM

No section 437.2.8.3 FBC building does not require a
Critical Branch distribution system. It sets requirements
for switching if one is provided. However, other codes may
require a Critical Branch distribution system.

Commentary

Typicaly all three would be required in a hospice care facility. Also the AHCA rules will require a complete essential system. See the definitions of the systems. All three subsystems serve a different purpose.