Interpretation #7099

Published October 24, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
4
Section
424.1.2.4
Topic
Tiles at water line

Question

Is it the intent that the exception in this section for the use of a dark color apply only to tiles installed to mark the water line and gutter lip, not the floor or walls of the pool?

Answer Published 10/24/2012 at 10:31 AM

Yes. The floor is to be a light color for safety reasons such
as providing contrast to allow lifeguards and others to
clearly see the people using the pool.
The Exception allows for the use of a dark color for tiles
installed to mark the water line or the gutter lip, not
the floor or walls of the pool.

Commentary

None.