Interpretation #7098

Published October 24, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
4
Section
404.6
Topic
Smoke Partition Doors

Question

Is it the intent of 404.6, exception 1 to not include the doors to comply with smoke partition requirements.

Answer Published 10/24/2012 at 10:30 AM

If there are glass doors in the glass wall, they would
need to be protected by sprinklers as for
the wall. Doors of other types would need
to be rated. NOTE: the section is
not calling for a smoke partition, but a
fire barrier. If the doors are glass they
are acting as a smoke barrier and must be
protected by the sprinklers like the glass
wall.

Commentary

None.