Interpretation #7097

Published October 24, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
4
Section
443.3.5.4
Topic
Shielding Devices

Question

Is it the intent of this section on shielding devices to require that if a person is standing at a hand dryer they cannot be seen from a corridor if there is no door on the restroom.

Answer Published 10/24/2012 at 10:29 AM

If the hand dryer is in the toilet
room, yes a partition or shielding
device is required. The code requires
to block the view of the occupants in
the toilet room, not from a particular
area in the toilet room.

Commentary

A shielding device is required by code, whether it is a door, partition or some other type of device to shield the occupants from view at all times while the occupants are inside the toilet room area. NOTE: 443 only applies to Schools, Colleges and Universities.