Interpretation #7089

Published October 24, 2012

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
6
Section
603.7
Topic
fire damper in metal duct

Question

Is it the intent of the mechanical code not to require a fire damper in a metal duct penetrating a wall separating a garage from a dwelling unit and what are the exceptions.

Answer Published 10/24/2012 at 10:26 AM

No fire damper is required in the duct
penetration from the garage to a
dwelling unit unless the building code
requires such wall to maintain a
specific fire resistance rating.

Commentary

This section of code assumes an unrated wall assembly between the dwelling unit and garage. The section intends to create a fire resistant barrier between the garage and dwelling unit without creating a specific rated assembly. As such, flexible duct may not be used to penetrate such walls. Some AHJs have allowed the use of 1- inch (minimum) fiberglass ductboard as an alternate to the minimum 26 ga. metal duct(see FBC-R section 302.5.2). However, this is a decision the local Building Official would have to make. BOAF has no position on the approval as an Alternate Method or Material based on the section quoted in this request.