Interpretation #7085

Published October 24, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
13
Section
101.4.7.1.1
Topic
duct repairs

Question

Is it the intent of 2010 Florida Building Code - Energy Conservation section 101.4.7.1.1 exception 3 to allow tests like blower door and repairs with other than fabric and mastic as allowed by the duct construction section 603 of the commercial code and section M1601.4 of the Residential code?

Answer Published 10/24/2012 at 10:21 AM

Yes, the duct system may be sealed
with any approved closure method as
specified in Energy Code Section
503.2.7.3.7 or Mechanical Code Table
603.

Commentary

The residential energy code refers to the commercial section for closure methods to prevent duplication of information since both residential and commercial have the same sealing requirements.