Interpretation #7084

Published October 24, 2012

Original Request

Code Version
2010
Code
FUELGAS
Code Description
Fuel Gas
Chapter
3
Section
310.1.1
Topic
CSST bonding

Question

Is it the intent of section 310.1.1 to require the bonding of all CSST piping even CSST gas appliance connectors to be with a minumum of #6 bonding jumper?

Answer Published 10/24/2012 at 10:20 AM

Section 310.1.1 requires the CSST gas
piping system to be "bonded to the
electrical service grounding electrode
system". This bonding shall also be in
compliance with the manufacturer's
installation instructions. Most
manufacturer's will require the bonding
wire to be routed to the bonding at the
main electrical panel or the main
grounding electrode of the service
panel. The use of bonding jumpers may
only be used when it does not conflict
with the CSST manufacturer's
installation and technical instructions
or the currently adopted version of
NFPA 70.

Commentary

Appliance flex connectors in compliance with FBC-FG Section 411 (except item #2) may be installed without the bonding unless the flexible connector manufacturer specifically requires the bonding. Those flexible connectors are "listed and labeled" for specific uses. CSST that is used in accordance with the manufacturer's instructions as an appliance connector would still fall subject to the code and manufacturer's requirement for bonding.