Interpretation #7070

Published September 27, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
15
Section
1509.7
Topic
roof curbs

Question

Is it the intent of the code to require engineering information on existing rooftop curbs which meet the existing code at the time of installation when applying for a permit to replace the HVAC unit. Not changes or alterations to existing curb.

Answer Published 09/27/2012 at 3:41 PM

102.8 Existing mechanical equipment. An agency or local
government may not require that existing mechanical
equipment on the surface of a roof be installed in
compliance with the requirements of the Florida Building
Code until the equipment is required to be removed or
replaced.

Commentary

This issue will fall to the Existing Building Code and the designer/contractor must select the code path within the Existing Building Code. That will then determine the amount of comliance with the FBC-M. If compliance through the Existing Building Code is done in accordance with Chapter 3, then all "new work, shall comply with the current FBC-M. The code offical may require anchoring information for the new unit to the existing curb (or adapter curb if provided). If the existing curb meets the height requiremetns of the code, is properly anchored through a previously permitted installation, and is not replaced, then it is allowed to remain in used without modification. If a new curb is installed, then all connections must be in compliance with the current codes.