Interpretation #7069

Published September 27, 2012

Download Final PDF

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
3
Section
306.1
Topic
working platform

Question

Is it the intent of 306.1 of the Mechanical code to have a working platform for condensers or is this just for furnaces and air handlers.

Answer Published 09/27/2012 at 12:01 PM

This requirement applies to "appliances"
as defined in the Code. Condensing
units are "appliances." A 30" x 30"
level working space is required. A
platform is not necessarily required.
The level working space could be the
ground, the floor, or a level rooftop

Commentary

The code is a minimum so please check the a/c manufacturer's installation requirements for possible additional working clearance requirements.