Interpretation #7060

Published August 13, 2012

Original Request

Code Version
2010
Code
PLUMBING
Code Description
Plumbing
Chapter
4
Section
416.5
Topic
tempering valves

Question

Is it the intent of 416.5 that each hand washing sink shall be supplied with seperate ASSE 1070 tempering valves? Or may several sinks be placed on the same ASSE 1070 valve if it is sized for maximum flow of fixtures it serves?

Answer Published 08/13/2012 at 4:30 PM

The Code is silent on the number of fixtures that may be
connected to a single tempering valve, therefore, the
choice of the number of lavatories that can be connected to
a single tempering valve is at the designer's discretion
and the manufacturers specs for the intended valve.

Commentary

None.