Interpretation #7059

Published August 13, 2012

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
10
Section
1021
Topic
Stair Enclosures

Question

Is it the intent of section 1021 exception 3 to allow the required stairs off of the second floor of a business occupancy to not be in a rated enclosure if they meet the travel distance requirements in section 1016?

Answer Published 08/13/2012 at 9:36 AM

Yes. Exit Access Stairs do not have requirements for fire
rated enclosure (that would be an Exit Stair enclosure). If
your Building has an automatic sprinkler system all access
from the second story can be via Exit Access Stairs;
otherwise 50%. Exit Access Stairs can be a vertical
component of a compliant Means of Egress.

Commentary

The stories cannot be open to each other.