Interpretation #7050

Published August 08, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
7
Section
712.2
Topic
Fire Resistant Rated Wall Sleeves

Question

Is it the intent of 712.2 to require sleeves through fire-resistance-rated walls constructed with metal studs and fire-rated sheetrock to be secured directly to the studs?

Answer Published 08/08/2012 at 4:56 PM

No, the testing is done without it being secured to the
studs. There may be a need to allow some flex for the caulk
to expand when attacked by the fire - must be installed per
manufacturer's listing/testing.

Commentary

None.