Interpretation #7042

Published August 08, 2012

Download Final PDF

Original Request

Code Version
2007
Code
ELECTRIC
Code Description
Electrical
Chapter
3
Section
table 300.5
Topic
PVC conduit

Question

Is it the intent of table 300.5 to require a schedule 40 PVC conduit to be installed at adepth of 24" as opposed to being encased in the 8" deep on ground concrete slab, as required by other sections of the FBC,for a nonresidential parking lot

Answer Published 08/08/2012 at 4:48 PM

Yes. Per Table 300.5, Column 3, The
2008 National Electrical Code requires
24" of cover.

Commentary

None.