Interpretation #7033

Published July 13, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Chapter
16
Section
1609.1.2
Topic

Question

1609.1.2 requires opening protection to meet the
requirements of ASTM E 1996. Is it the intent of the
code that opening protection meet the optional wind
zone 4 criteria of ASTM E 1996 sections 7.2 and 8.4?

Answer Published 07/13/2012 at 9:06 AM

No, as stated in the standard, Wind Zone 4 is optional. The
Florida Building Commission approved a glitch amendment in
June to the building and residential codes realigning Wind
Zone 4 changing the trigger wind speed to 170 mph to apply
to Miami-Dade and a portion of Monroe Counties.

Commentary

The intent of ASTM E 1996 Committee in adopting Wind Zone 4 was to address Miami-Dade County protocols.