Interpretation #7004

Published May 18, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
7
Section
709.1
Topic
tenant separation in highrise bldg

Question

Is it the intent of The FBC to remove the requirement for tenant seperation in Highrise construction where there would be multiple tenants on a floor. It appears there is a conflict in the exceptions. Exception one states the old 3000sqft rule but the new exception four states in other than dwelling and sleeping units if fire sprinklers are installed in accordance with 903.3.1.1 fire rated partitions would not be required.

Answer Published 05/18/2012 at 8:45 AM

Yes.

Commentary

The Exceptions stand alone. The 3000 sq ft limit does not apply in fully sprinklered buidings. The base requirement is one hour separation. Then each of the Exceptions is a separate entity. There is no "and" after the Exceptions binding them together; nor are the Exceptions requirements. They are exceptions to the requirement for a one hour fire-resistance rating.