Interpretation #6999

Published June 13, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
3
Section
304
Topic
Adult Education Program

Question

Is it the intent of section 304 to classify an adult education program on a high school campus as Business Occupancy or can it be classified as Educational?

Answer Published 06/13/2012 at 1:27 PM

The proper occupancy classification for an adult education
program is Business as 304.1 specifically calls
out "Educational occupancies for students above the 12th
grade."

Commentary

There is no simple answer to the question without further information. If the Adult Ed classes are regular K-12 classrooms than it is an Educational Occupancy. If the classes are taught in buildings that are used for non-adult students than the building is an Educational occupany and the Adult Ed is accessory to the Educational occupancy. If the Adult Ed classes are other than k-12 classes and the adult students are being taught in their own building than Business occupancy would be appropriate.