Interpretation #6998

Published May 18, 2012

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
44
Section
4409.5.1.1, 4403.16.1a, 4
Topic

Question

Is it the intent of this code section to use rational analysis when designing exterior 2x4 walls?

Answer Published 05/18/2012 at 8:47 AM

Yes.

Commentary

Section R4409.5.1.1 allows the studs in exterior walls to be less than 2 x 6 only if designed by rational analysis by a licensed professional engineer or architect proficient in structural design. Rational analysis must demonstrate compliance with the structural requirements of R4403. Minimum sizes may not be sufficient in all cases; therefore, a rational analysis is required to ensure design loads are complied with. Compliance with R4403, R4409 and all of the other conditions contained in section R4403.16.4 (2) is the means to obtain an exemption from the testing requirements of section R4403.16.1.