Interpretation #6994

Published June 13, 2012

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
16
Section
1626.2.4
Topic
Large Missile impact test

Question

Is it the intent of Section 1626.2.4 to allow the large missile to impact the test specimen at other than 90 degrees to the surface?

Answer Published 06/13/2012 at 1:41 PM

No. Based on previous clarifications to Florida Building
Code Test Protocols for the High Velocity Hurricane Zone
TAS201 TESTING APPLICATION STANDARD (TAS) 201-94 IMPACT
TEST PROCEDURES and PA201 dating back to 1994, the large
missile cannon can be fired at a vertical angle to
compensate for the missile drop causing a perpendicular
impact to the specimen. It has also been clarified for
laboratories accredited to perform TAS201 that the front of
the missile cannon can be shimmed as a means to cause a
perpendicular impact to the specimen.

Commentary

The barrel of the large missile cannon shall be mounted on a support frame in a manner to facilitate aiming the missle so that it impacts the specimen at the desired location from 9 feet away plus the length of the missile.