Interpretation #6992

Published June 13, 2012

Original Request

Code Version
2010
Code
PLUMBING
Code Description
Plumbing
Chapter
4
Section
403.1, 415 & 418
Topic
service sink

Question

Is it the intent of 403.1 A-3 (church) minimum requirement of a service sink to do double duty with a two compartment sink in a break area with microwave ovens and refrigerator?

Answer Published 06/13/2012 at 1:45 PM

No, table 403.1 Plumbing, uses the term "service sink" and
not just "sink" for the specific identification
of "service" which is defined as applied to repair or
provide maintenance. The intent is for the service sink
(mop sink) to rinse out dirty mop soaked with chemicals
associated with service to be clearly different than a sink
used to wash hands, vegetables, and dishes that are
associated with a break room.

Commentary

None.