Interpretation #6976

Published April 27, 2012

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
4
Section
403.3
Topic
T 403.3

Question

Is it the intent of the modification to the wording on note "h" in Table 403.3 to change the requirements for Nail Salons or to Clarify the existing 2007 Mechanical Code reqirements?

Answer Published 04/27/2012 at 4:37 PM

Yes. There is an increase to 50 CFM per station. The
source capture system is required IN ADDITION to the other
403.3 requirements for nail salons. A ventilation table OR
other exhaust system that captures the odors or
contaminants at the sourse can be used to achieve code
compliance.

Commentary

This section is referencing the fact that some nail tables have a built-in exhaust system as part of the table design. Otherwise, the exhaust system could be any other system which can capture the odors or contaminants at the source which is at the table height not at the ceiling level. The exhaust must be a minimum of 50 CFM's per station. The 2010 FMC 403.3 clarifies and emphasizes the requirement for capturing the odors or contaminants at the source.