Interpretation #6968

Published April 26, 2012

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
4
Section
R401.3
Topic
Drain Surface Water - Foundation

Question

Is it the intent of section R401.3 to be applicable to the exterior vertical face of monolithic slab foundations in the requiremnt to drain surface water away from "foundation walls"?

Answer Published 04/26/2012 at 10:02 AM

Yes, drainage away from the foundation is required.

Commentary

The slope away from the building is required to be 6 inches within the first 10 feet. The exception allows for use of drains and swales if lot lines or physical barriers, such as a steeply sloping lot, do not allow for a 6" slope, then the minimum slope is 2 percent.